Below are some commonly asked questions about underfloor air conditioning.
If your question is not listed here, please contact us.
Below are some commonly asked questions about underfloor air conditioning.
If your question is not listed here, please contact us.
Yes, the raised access floor creates the plenum which is used as the ventilation zone for air circulation and distribution
Most raised access floor systems with a robust substructure are suitable, but pedestals and stringers must be checked to ensure compatibility
A floor depth of 300 mm is required for a standard AET TU-4 Fantile, or as low as 180 mm is possible with the slimline TU-S Fantile
The grilles have been designed to stop pens and pencils falling through. The nominal gap between the bars is 6.3mm / 6.4mm and can be walked upon with most high heel shoes.
Compared to the area taken up by the large air ducts of an air only system, the loss of lettable space is less with AET Flexible Space.
Cooling depends on space temperatures, water temperatures, water flows etc. but generally the AET Flexible Space system can accommodate loads of up to 200 W/sq m. AET will select CAM’s and specify the number of Fantiles required.
If the fan terminals are correctly located, draughts will not be an issue for users. Watch the smoke test video to understand more about the air dispersion.
Dust and dirt build up is possible depending on the use of the space and typical cleaning schedule, however Fantile units are easily cleaned by simply lifting the grille and vacuuming. Any particles that enter the return path are filtered out by the CAM.
A fire-resistant air segregation baffle made from silicone cloth is installed in the void to create supply and return air paths
UfAC systems are generally more expensive then Fan Coil units and cheaper than conventional ceiling based VAV systems. When considering total cost of construction UfAC systems are typically more economical.
The systems has operated in a wide range of climatic conditions from -20 deg C and +50 deg C and condensation has not been found to be a problem
As there is little or no ductwork in underfloor plenums the noise generated can be substantially less than that from a conventional ducted system. Sound transmission or cross talk between offices can be a concern but this can be minimised with the correct choice of partition and quality of seals. Additional sound baffles can be installed in ceiling voids.
After the initial thermal mass has charged and the building has settled, it may be possible to run the system for less hours due to the thermal flywheel effect. Free cooling may also be implemented where suitable outside temperatures exist.
Each country has their own fire safety measures for underfloor plenum. Most floor tiles meet fire rating requirements and generally applicable codes state that placing wires and cabling in an air supply plenum is not a problem where they are placed inside a conduit or rated to be non-combustible.
Contact us to discuss your HVAC requirements
See how UfAC can speed up construction time, reduce costs and create space.